AL2336

IOL MOD SL 6XDO/DO E D M12 IP67

IO-Link CompactLine module

AL2336

IOL MOD SL 6XDO/DO E D M12 IP67

  • Six ports with two binary outputs each for twelve actuators
  • Two separate voltage supplies rated up to 1.8 A each
  • Robust design for use in harsh industrial environments
  • For easy control of actuators on any IO-Link masters
  • Data and energy transmission also possible with unscreened connection cable
  • ce
  • ukca
  • iolink
  • cul
Application
Application I/O modules for field applications
Electrical data
Operating voltage [V] 18...30 DC; (US)
Current consumption [mA] 50; (US)
Protection class III
Additional voltage supply [V] 18...30 DC; (UA)
Max. current consumption from additional supply [mA] 3600; (UA)
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 12
Outputs
Number of digital outputs 12; (6 x 2)
Output function PNP
Max. current load per output [mA] 1800
Max. current load outputs total [A] 3.6; (Max. current load per output side: 1800 mA)
Electrically separated yes
Interfaces
Communication interface IO-Link
Supported DeviceIDs
Type of operation DeviceID
default 893
IO-Link Device
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode no
Min. process cycle time [ms] 5.6
Operating conditions
Ambient temperature [°C] -25...60
Storage temperature [°C] -25...70
Max. relative air humidity [%] 90
Max. height above sea level [m] 2000
Protection IP 65; IP 67
Protection rating (NEMA 250) 6P
Pollution degree 2
Chemical media
ISO 16750-5 AA, BA, BD, HLP, CC, DB, DC, DD, CA
NEMA 250 5.13.1 AA
Tests / approvals
EMC
EN 61000-6-2
EN 61000-6-3
IEC 61131-9
Shock resistance
DIN EN 60068-2-27
Vibration resistance
DIN EN 60068-2-64
DIN EN 60068-2-6
Mechanical data
Weight [g] 308.8
Dimensions [mm] 26 x 59.3 x 152
Materials housing: PA; socket: brass nickel-plated
Sealing material FKM
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Accessories
Accessories (optional)
Protective caps M12
Remarks
Remarks
Using the device within a system with requirements for functional safety is possible by deactivating the actuator voltage UA without interaction.
For further information on functional safety, please refer to the operating instructions supplement under “Downloads”.
Pack quantity 1 pcs.
Electrical connection - IO-Link
X1 Connector: M12; coding: A
Electrical connection - Outputs
X1.0...X1.5 Connector: M12; coding: A; Sealing: FKM
Electrical connection - power supply
X31 Connector: M12; coding: A