Electrical data
Operating voltage [V] |
21.6...26.4 DC; (to SELV/PELV) |
Nominal voltage DC [V] |
24 |
Current consumption [mA] |
< 1230 |
Max. current load total [A] |
1.2 |
Inputs / outputs
Number of inputs and outputs |
Number of digital inputs: 3; Number of digital outputs: 4 |
Inputs
Number of digital inputs |
3 |
Switching level high [V] |
11...26.4 |
Switching level low [V] |
0...5 |
Outputs
Output signal |
switching signal |
Number of digital outputs |
4 |
Max. current load per output [mA] |
400; 640; (400 mA: red; green; blue; 640 mA: white) |
Max. current load outputs total [A] |
1.2 |
Short-circuit proof |
yes |
Interfaces
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Function class |
Designation |
0x4000 |
Identification and Diagnosis |
|
SIO mode |
yes |
Required master port type |
A |
Min. process cycle time [ms] |
4.2 |
Supported DeviceIDs |
Type of operation |
DeviceID |
default |
1474 |
|
Note |
For further information please see the IODD PDF file under "Downloads" |
|
Operating conditions
Ambient temperature [°C] |
-25...60 |
Storage temperature [°C] |
-25...60 |
Max. relative air humidity [%] |
90; (linearly decreasing to 50 % (40 °C); non condensing) |
Max. height above sea level [m] |
2000 |
Protection |
IP 65; IP 67 |
Pollution degree |
2 |
Mechanical data
Weight [g] |
130.2 |
Weight (without accessories and packaging) [g] |
0.001 |
Dimensions [mm] |
99.1 x 50 x 31 |
Materials |
housing: PA; cover: PA; Sealing cover: TPE |
Sealing material |
FKM |
Displays / operating elements
Remarks
Remarks |
Please observe the permissible voltage ranges of the connected devices, as these may differ from the IO-Link specification. |
For further information please see the operating instructions. |
|
Pack quantity |
1 pcs. |
Electrical connection - socket
|
Connector: 1 x M12; coding: A; Sealing: FKM |
Electrical connection - plug
IO-Link operation |
Connector: 1 x M12; coding: A |