• Products
  • Industries
  • IIoT & Solutions
  • Service
  • Company
  1. Products
  2. IO-Link
  3. IO-Link position sensors
  4. IO-Link - Position sensors for valve actuators
  5. MVQ301

Positioner for industrial valves

MVQ301

MVQ3360-XRKG/IO/B-Port/2SV/US

Positioner for industrial valves

MVQ301

MVQ3360-XRKG/IO/B-Port/2SV/US

  • Integrated adjustment algorithm with self-optimisation for positioning of industrial valves accurate to a percentage
  • Automatic Teach-In function for fast set-up
  • Reduced wiring due to direct control of the control valve
  • Self-diagnostics regarding wear, blockages or deposits for preventive maintenance
  • Individually adjustable RGB LED with flashing mode for easy visual localisation in challenging environments
The above price does not include 24% VAT

To ensure the correct functioning of the device, we strongly recommend purchasing one of the complete positioner sets for the initial setup. Click here for an overview.

  • ce
  • ukca
  • iolink
Product characteristics
Communication interface IO-Link
Housing rectangular
Dimensions [mm] 95 x 50 x 57
Solenoid valve connection (SV1 / SV2)
Electrical design PNP
Output function 2 x normally open
Application
Operating principle magnetic
Application angle of rotation detection absolute; position control
Electrical data
Protection class III
Reverse polarity protection yes
Max. power-on delay time [ms] 300
Actuator supply (UA)
Operating voltage [V] 20...30 DC
Current consumption [mA] < 410
Sensor supply (US)
Operating voltage [V] 20...30 DC
Current consumption [mA] < 40
Outputs
Solenoid valve connection (SV1 / SV2)
Electrical design PNP
Output function 2 x normally open
Max. current load per output [mA] 200
Short-circuit protection yes
Overload protection yes
Detection zone
Detection zone [°] 360
Accuracy / deviations
Rotational angle detection
Accuracy [°] ± 1
Temperature drift [°/K] 0,02
Repeatability [°] 0,1
Position control
Deadband
0,5...25 % (Factory setting: 2 %)
Resolution [%] 0,1; (preset value)
Switch point indication
Hysteresis [%] 0.4...10; (Factory setting: 1 %)
Open
1...100 % (Factory setting: 95 %)
Closed
0,0...99,0 % (Factory setting: 5 %)
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles
Function class Designation
0x0030 BLOB transfer
0x4000 Identification and Diagnosis
0x8101 Locator
0x8102 ProductURI
SIO mode no
Required master port type B
Min. process cycle time [ms] 6
Supported DeviceIDs
Type of operation DeviceID
default 1775
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 65; IP 67; (Target puck area dust-protected)
Tests / approvals
EMC
EN 61000-4-2 4 kV CD / 8 kV AD
EN 61000-4-3 10 V/m
EN 61000-4-4 2 kV
EN 61000-4-6 10 V
EN 55011 class B
Vibration resistance
EN 60068-2-6 Fc 1 mm (10...55 Hz) / 1 octave per minute in 3 axes
Shock resistance
EN 60068-2-27 Ea 30 g 11 ms half sine; 6 shocks each in every direction along the three coordinate axes
MTTF [years] 421
Embedded software included yes
Mechanical data
Weight [g] 188.8
Housing rectangular
Dimensions [mm] 95 x 50 x 57
Materials housing, target puck: PA; plug, socket: stainless steel (316L / 1.4404)
Tightening torque [Nm] target puck: 1,2; housing: 3,0; housing on plastic mounting plate: 1,5
Displays / operating elements
Display
operation 1 x LED, green
switching status 3 x LED, white
switching status 1 x LED, RGB
Accessories
Items supplied
socket head screws: 4 x M5 x 16, stainless steel
Remarks
Pack quantity 1 pcs.