Application
Design |
only for operation with AS-i masters with the profile M4, for the connection of mechanical contacts a suitable sensor is to be connected to any input |
Application |
field installation |
Electrical data
Operating voltage [V] |
26.5...31.6 DC |
Max. current consumption from AS-i [mA] |
230 |
Additional voltage supply [V] |
15...30 DC; (AUX) |
Max. current consumption from additional supply [mA] |
1000; (AUX; < 40 °C: 2 A) |
Integrated watchdog |
yes |
Inputs / outputs
Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
Inputs
Number of digital inputs |
4 |
Input circuit of digital inputs |
PNP; (type 2 according to IEC 61131-2) |
Sensor supply of the inputs |
AS-i |
Power supply [V] |
18...30; (DC) |
Max. total current rating of inputs [mA] |
180 |
Input current High [mA] |
6...10 |
Input current Low [mA] |
0...2 |
Switching level high [V] |
> 11 |
Digital inputs protected against short circuits |
yes |
Outputs
Number of digital outputs |
4 |
Circuit |
PNP |
Voltage range DC [V] |
15...30; (AUX) |
Max. current load per output [mA] |
500; (< 40 °C: 1000 mA) |
Short-circuit proof |
yes |
Electrically separated |
yes |
Actuator supply outputs |
AUX |
Operating conditions
Ambient temperature [°C] |
-25...60 |
Storage temperature [°C] |
-25...60 |
Max. relative air humidity [%] |
90; (non condensing) |
Max. height above sea level [m] |
2000 |
Protection |
IP 65; IP 67; IP 68 |
Tests / approvals
EMC |
|
MTTF [years] |
278 |
UL approval |
|
AS-i classification
AS-i version |
3.0 |
Extended addressing mode |
yes |
AS-i master profile |
M4 |
AS-i profile |
S-7.A.7 |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
A.7 |
Assignment of the data bits |
data bit |
D0 |
D1 |
D2 |
D3 |
input |
1 |
2 |
3 |
4 |
socket |
I-1 |
I-2 |
I-3 |
I-4 |
pin |
4 |
4 |
4 |
4 |
Output |
1 |
2 |
3 |
4 |
socket |
O-1 |
O-2 |
O-3 |
O-4 |
pin |
4 |
4 |
4 |
4 |
|
Assignment of the parameter bits |
parameter bit |
Designation |
|
|
|
|
|
P0 |
not used |
|
|
|
|
|
P1 |
peripheral fault indication |
: 1 |
activated |
/ 0 |
deactivated |
|
P2 |
not used |
|
|
|
|
|
P3 |
not used |
|
|
|
|
|
|
Mechanical data
Weight [g] |
150 |
Type of mounting |
backplane mounting |
Dimensions [mm] |
134.5 x 30 x 23.5 |
Materials |
PBT |
Displays / operating elements
Display |
switching status |
LED, yellow I1...I4, O1...O4 |
operation |
LED, green AS-i, AUX |
errors |
LED, red |
|
Accessories
Items supplied |
Label tags |
Protective caps: 2 |
|
Accessories (optional) |
Protective cap: M8, E73005 |
Flat cable insulation displacement connector: 1 m, round cable, E70582 |
DIN rail adapter:, E73007 |
|
Remarks
Remarks |
Do not connect any of the following points to an external potential: |
I-, I+, I1, I2, I3, I4 |
The connections are electrically connected with the AS-i cable. |
|
Pack quantity |
1 pcs. |
Electrical connection - AS-i
|
Connector: 1 x M12; coding: A |
Electrical connection - Inputs
|
Connector: 4 x M8; coding: A |
Electrical connection - Outputs
|
Connector: 4 x M8; coding: A |